Skip to Content.
Sympa Menu

proscan-opinfo-elog - [Proscan-opinfo-elog] ELOG Proscan: Problem Kontrollsysteme: G2 Meldet interlok HMF1A

proscan-opinfo-elog AT lists.psi.ch

Subject: Proscan-opinfo-elog mailing list

List archive

[Proscan-opinfo-elog] ELOG Proscan: Problem Kontrollsysteme: G2 Meldet interlok HMF1A


Chronological Thread 
  • From: Lutz Hubert (LH84) <hubert.lutz AT psi.ch>
  • To: proscan-opinfo-elog AT lists.psi.ch, "D'Amico Michael (DC84)" <michael.damico AT psi.ch>
  • Subject: [Proscan-opinfo-elog] ELOG Proscan: Problem Kontrollsysteme: G2 Meldet interlok HMF1A
  • Date: Wed, 18 Feb 2015 08:35:44 +0100
  • List-archive: <https://lists.web.psi.ch/pipermail/proscan-opinfo-elog/>
  • List-id: <proscan-opinfo-elog.lists.psi.ch>

Title: ELOG
Eintrag   Tue 17-Feb-15 08:07, Barchetti, Mäder, Vonarburg, Problem, Verzögerung, Kontrollsysteme, "G2 Meldet interlok HMF1A" 
    Antworten   Wed 18-Feb-15 08:35, Lutz Hubert (LH84), Problem, Verzögerung, Kontrollsysteme, "G2 Meldet interlok HMF1A" 
Ein neuer ELOG Eintrag wurde eingegeben:
Logbuch: Proscan  Eintrag-ID: 22046    Eingabezeit: Wed 18-Feb-15 08:35     Als Antwort auf: 22040
Wann:Tue 17-Feb-15 08:03 
Autor: Lutz Hubert (LH84) 
Eintrag: Problem 
System: Kontrollsysteme 
Effekt: Verzögerung 
Titel: G2 Meldet interlok HMF1A 

 

Barchetti, Mäder, Vonarburg schrieb:

HMF1A:SOL:1 reagierte wie Ampere anstelle von DAC.
Auch Max & Min Werte waren auf 0

--> Reboot Prof23 auf anweisung von Controls
--> Fehler behoben DAC / Min & Max Werte wieder IO

Zur Info : In einem solchen Fall (d.h Min % Max Werte = 0) ist es ausreichend die Funktion RESET-DSP ausfuehren

entweder : caput MAGNET:COM:2 RESET-DSP oder das Tool caview verwenden !

 

 

ELOG V2.9.2-ebb441c



Archive powered by MHonArc 2.6.19.

Top of Page